Overview
Long wire runs lose voltage, so lights dim and motors run hot. This calculator estimates voltage drop from the conductor material, wire gauge, current and distance.
The common guideline is no more than 3% drop on a branch circuit and 5% in total from the service to the load.
Worked examples
| Inputs | Result |
|---|---|
| UnitsImperial (ft, miles, gallons)ConductorCopperWire size12 AWGCurrent (A)16One-way length (ft or m)100Circuit voltage (V)120PhaseSingle phase | Voltage drop: 6.32 V (5.27%)Voltage at load: 113.68 VOver 5%: use a larger wire size or shorten the run. |
Show 2 more examples
| UnitsImperial (ft, miles, gallons)ConductorCopperWire size8 AWGCurrent (A)20One-way length (ft or m)100Circuit voltage (V)120PhaseSingle phase | Voltage drop: 3.13 V (2.6%)Voltage at load: 116.87 VWithin the 3% guideline for branch circuits. |
| UnitsImperial (ft, miles, gallons)ConductorAluminumWire size2 AWGCurrent (A)60One-way length (ft or m)150Circuit voltage (V)240PhaseSingle phase | Voltage drop: 5.75 V (2.4%)Voltage at load: 234.25 VWithin the 3% guideline for branch circuits. |
Voltage drop by current
With the calculator's starting values, the voltage drop is 6.32 V. The table shows how it changes with the current.
| Current (A) | Voltage drop |
|---|---|
| 8 | 3.16 V |
| 10 | 3.95 V |
| 12 | 4.74 V |
| 14 | 5.53 V |
| 16starting value | 6.32 V |
| 18 | 7.11 V |
| 20 | 7.9 V |
| 22 | 8.69 V |
| 24 | 9.48 V |
Other inputs: Units: Imperial (ft, miles, gallons) · Conductor: Copper · Wire size: 12 AWG · One-way length: 100 ft · Circuit voltage: 120 V · Phase: Single phase. Change them in the calculator above for your own numbers.
How it works
Voltage drop = multiplier × K × I × L ÷ CM. K is the resistivity of the conductor (12.9 Ω·cmil/ft for copper, 21.2 for aluminum), I the current, L the one-way length and CM the wire’s circular-mil area. The multiplier is 2 for single phase and √3 for three phase.
The formula
| K | 12.9 (copper) or 21.2 (aluminum) Ω·cmil/ft at about 75 °C |
| I | Load current in amps |
| L | One-way length in feet |
| CM | Circular mils of the wire gauge |
Practical tips
- Voltage drop is a performance check, not ampacity. The wire must also be rated for the current.
- Use the continuous load current, not the breaker size, for a realistic figure.
- Have a licensed electrician confirm sizing for anything connected to your panel.
Frequently asked questions
What is acceptable voltage drop?
The NEC recommends 3% or less on branch circuits and 5% or less overall.
What wire size for 100 ft at 20 A, 120 V?
12 AWG copper drops about 7.9 V (6.6%). 8 AWG brings it down to about 3.1 V (2.6%).