Overview
Electrical code limits how full a conduit can be, so wires can be pulled safely and stay cool. This checks THHN wires in EMT against the 40% limit.
Choose the conduit size, wire size and wire count. It handles three or more wires of the same size.
Worked examples
| Inputs | Result |
|---|---|
| EMT trade size1/2 inTHHN wire size12 AWGNumber of wires9 | Fill: 39.4%Within the 40% limitMaximum wires of this size: 9Same size wires only. Check local code, and ampacity derating for bundled wires. |
Show 2 more examples
| EMT trade size3/4 inTHHN wire size12 AWGNumber of wires16 | Fill: 39.9%Within the 40% limitMaximum wires of this size: 16Same size wires only. Check local code, and ampacity derating for bundled wires. |
| EMT trade size1 inTHHN wire size8 AWGNumber of wires8 | Fill: 33.9%Within the 40% limitMaximum wires of this size: 9Same size wires only. Check local code, and ampacity derating for bundled wires. |
Fill by number of wires
With the calculator's starting values, the fill is 39.4%. The table shows how it changes with the number of wires.
| Number of wires | Fill |
|---|---|
| 6 | 26.3% |
| 8 | 35% |
| 9starting value | 39.4% |
| 10 | 43.8% |
| 12 | 52.5% |
Other inputs: EMT trade size: 1/2 in · THHN wire size: 12 AWG. Change them in the calculator above for your own numbers.
How it works
Fill is the total cross-section of the wires divided by the conduit’s inside area. With three or more wires, NEC limits fill to 40%. The areas used are NEC figures for EMT and THHN. A full conduit may also need ampacity derating, which this doesn’t calculate. Have a licensed electrician confirm the design against your local code.
The formula
| wire area | Per wire, in sq in, from NEC tables |
| conduit area | Inside area, in sq in |
Practical tips
- Nine 12 AWG THHN wires fit in 1/2 in EMT at 39.4% fill.
- Long or curvy runs are easier to pull with a size larger.
- More than three current-carrying wires may reduce their allowed ampacity.
Frequently asked questions
Why is the limit 40%?
It leaves room to pull wires without damage and lets heat escape. One wire may fill 53%, and two may fill 31%.
Does this work for other conduit types?
No. PVC and other types have different inside areas, so use the matching NEC table.