Overview
Power factor shows how much of the current actually does useful work. Low power factor means higher currents and sometimes utility penalties.
Enter the real and apparent power, plus a target.
Worked examples
| Inputs | Result |
|---|---|
| Real power (kW)10Apparent power (kVA)12.5Target power factor0.95 | Power factor: 0.8Reactive power: 7.5 kVARPhase angle: 36.87°To reach 0.95: add 4.213 kVAR of capacitors |
Show 2 more examples
| Real power (kW)50Apparent power (kVA)70Target power factor0.95 | Power factor: 0.714Reactive power: 48.99 kVARPhase angle: 44.42°To reach 0.95: add 32.56 kVAR of capacitors |
| Real power (kW)8Apparent power (kVA)8.5Target power factor0.9 | Power factor: 0.941Reactive power: 2.872 kVARPhase angle: 19.75°Already at or above 0.9. |
Power factor by real power
With the calculator's starting values, the power factor is 0.8. The table shows how it changes with the real power.
| Real power (kW) | Power factor |
|---|---|
| 6 | 0.48 |
| 8 | 0.64 |
| 10starting value | 0.8 |
| 12 | 0.96 |
Other inputs: Apparent power: 12.5 kVA · Target power factor: 0.95. Change them in the calculator above for your own numbers.
How it works
PF = kW ÷ kVA. Reactive power = √(kVA² − kW²). Capacitors can supply the reactive power that a target requires.
The formula
| kVAR | Reactive power |
Practical tips
- 10 kW and 12.5 kVA give a PF of 0.8; reaching 0.95 needs about 4.2 kVAR of capacitors.
- Motors at light load usually have low power factor.
- Many utilities charge commercial users for low power factor.
Frequently asked questions
What is a good power factor?
About 0.95 or higher.
Does correction save home energy?
Rarely, since homes are usually billed on real power.